Dranetz HDPQ® Xplorer 400 SP
(Rated IP65) 

Designed for Commercial, Military, Aviation, and Naval Industries with 400Hz Monitoring Capability!

The Dranetz HDPQ Xplorer 400 SP (IP65) power quality analyzer takes PQ, Demand and Energy monitoring to new heights by adding 400Hz monitoring capabilities to the already powerful Dranetz HDPQ Xplorer SP. The Dranetz HDPQ Xplorer 400 SP is designed for applications such as aviation, naval, military, etc. requiring 400Hz capabilities that are not available in most PQ and Energy analyzers which typically only measure 50/60Hz. The Dranetz HDPQ Xplorer 400 SP is also an all-purpose tool that can be used for any traditional 50/60Hz application. In addition to the 400Hz applications, the Dranetz HDPQ Xplorer 400 SP is perfect for applications such as power quality surveys, voltage and current transient studies, fault recording, inrush, motor testing, harmonic analysis, advanced distortion analysis, demand/energy/load studies, and many more.

The Dranetz HDPQ Xplorer 400 SP has the same measurement and communications capabilities as the HDPQ Xplorer 400 Plus, but is housed in an IP65 enclosure without an LCD display, and can also be powered by the circuit being measured. The IP65 enclosure of the Dranetz HDPQ Xplorer 400 SP greatly expands the applications of the Dranetz HDPQ Xplorer into outdoor and harsh environments, along with other applications where an LCD display is undesirable.

The Dranetz HDPQ Xplorer 400 SP offers best in class PQ monitoring capabilities. It measures to all current industry standards, including IEC 61000-4-30 Class A Edition 31, IEC 61000-4-7, IEEE 1159, IEEE 519:2014, IEEE 1459, and more. With its high speed transient data capture (1 microsecond/channel) capabilities, this 8-channel workhorse won’t miss a PQ event. It simultaneously captures and characterizes thousands of parameters by using a range of standard and customizable operating modes. The unique measurement capabilities include the capture of low-medium-high frequency transients through peak, waveshape, rms duration and adaptive high-speed sampling, as well as power measurements to clearly characterize harmonics, non-sinusoidal, and unbalanced systems. The Intelligent AnswerModule® feature provides consultant-like analysis of sag directivity, capacitor switching transient identification/directivity and motor analysis/reporting.

The Dranetz HDPQ Xplorer 400 SP enables users to review data and change settings remotely from virtually any smartphone, tablet and mobile device, as well as with traditional PC and MAC laptops and desktops. Just hook up the instrument, close the cabinets to the ‘safe’ environment, and review data and control the instrument using either the VNC interface in our Dran-View 7 software or a free VNC client on your Smartphone or Tablet from anywhere with connectivity to the instrument.

Mobirise

Description

• Detects & records sags/dips, swells, interruptions, transients, harmonics, flicker, RVC and more – Meets & Exceeds Industry Standards
• Tests 400 Hz & 50/60Hz – Specialized Aircraft, Naval and Other Applications and Standard Power Monitoring
• High Speed Transient Capture – Don’t Miss a PQ Event
• IEC 61000-4-30 Class A Edition 3 PQ compliant – Reliable Measurements from a Reputable Manufacturer
• Power Quality, demand & energy analysis – Complete Power Monitoring Surveys
• Measures, records and triggers on power parameters such as V, I, W, VA, VAR, PF, demand, energy & more
• Powered by the Phase Being Measured!
• IP65 enclosure
• Dran-View 7 Software – Powerful Data Analysis, Reporting & Remote Control
• Ethernet & Wireless Communications for Remote Control & Data Downloading – Be Safe & Productive
Power the instrument from the circuit being measured, or another source

Dranetz HDPQ Xplorer 400 SP – Precision

• High Definition PQ & Energy Monitoring – 1000Vrms, AC/DC, 512 samples/cycle
• High Speed Digitized Transients – 1us, 10 to 2000Vpk
• 50/60Hz and 400Hz operating modes
• Eight channels, 4 voltage & 4 current
• AnswerModules – Sag directivity, PF capacitor identification, motor – automatic event categorization
• Advanced PQ – IEC 61000-4-30 Class A Ed 31 & IEEE 1159 compliant
• Harmonics – IEC 61000-4-7, IEEE 519 (2014)
• Transient capabilities – V & I – waveshape triggers, high speed. Well beyond standards requirements
• IEEE 1459 Advanced Power Measurements
• 10,000 cycle pre/post trigger buffer
• EN 50160 Ed 3

Dranetz HDPQ Xplorer 400 SP – User Interface

• Automatic setups – PQ, Demand and Energy
• Tablet-like GUI that is icon driven, has taskbar shortcuts, and a Dashboard (only available remotely on the Dranetz HDPQ Xplorer 400 SP)

Dranetz HDPQ Xplorer 400 SP – Communications

• Ethernet, Wi-Fi, USB, Bluetooth (optional)
• VNC for full remote control from Dran-View 7 or a 3rd party App
• Apple & Android apps with real time metering and alarm Dashboard

Dranetz HDPQ Xplorer 400 SP – Safe & Rugged

• Arc Flash Safety
• UL/cUL listed and CE approved
• IP65 enclosure for harsh and outdoor environments
• Automatic circuit detection and feedback on proper connection of the instrument User Interface

Dranetz HDPQ Xplorer 400 SP – Productivity

• Mini-report – Screen snapshots, XML file. Easily uploaded and emailed!
• PQ & energy Dashboard’s for real time alarming
• AnswerModules – automatic event categorization
• Dran-View 7 power quality analysis software
• Rescue kit – Part of Dran-View 7. Correct problems with wiring, CT orientation, time errors and more
• Post processing – Part of Dran-View 7. Compute harmonics and other parameters from the waveforms recorded by the instrument

(4) Differential Voltage: 512 samples/cycle, 16 bit resolution
• 40-1000Vrms, +/- 0.1% reading. <40V +/- 0.1% reading +/- 0.05% FS
• IEC 61000-4-30 Class A Ed 31: 60-1000Vrms, ±0.1 % of Udin, range of 10% – 150% of Udin
• Transients – rms: 0-1414Vpk, ±0.2 % of Udin
• Transients – High Speed: 10-2000Vpk, +/- 10% of reading, +/- 0.5% FS

(4) Current: 512 samples/cycle, 16 bit resolution
• Range (rms) probe dependent, +/- 0.1% reading +/- 0.05% FS
• Transients – Range probe dependent
• Transients – High Speed: Range probe dependent., 10% of Reading, +/- 0.5%FS


Frequency: 10 sec window
• 2.5-69Hz, +/- 0.01Hz, 380-420Hz +/- 0.1Hz

Dranetz HDPQ Xplorer 400 SP (IP65)
• Size: (11″w x 6.5″h x 2.5″d), (27.9cm x 16.5cm x 6.4cm)
• Weight: 3.8lbs, 1.72kg
• Operating temperature: -10 to 50 deg C (14 to 122 deg F)
• Storage temperature: -40 to 85 deg C (-40 to 185 deg F)
• Humidity: 10-90 non condensing
Power Supply: 90-600VAC/500VDC (50/60Hz). Powered by the phase being measured, or other source

Clock accuracy and resolution
• Internal: +/- 1 sec/day at 25 deg C
• NTP: +/-10 msec
• GPS: +/-1 msec

AC Adapter: 100-240Vac 50/60Hz

Battery capacity and charge time:
• Dranetz HDPQ Xplorer 400 SP: 30 minutes run time on full charge, 3 hours charge time

Memory size: 4GB

Display: 7” WVGA color graphic, Icon based touch LCD, LED Backlit
Languages: English, German, Spanish, French, Italian, Swedish, Finnish, Polish, Chinese (traditional and simplified), Thai, Korean

• Ethernet, 802.11 b/g/n Wireless (available without Wi-Fi as a special order)
• USB On the Go
• Bluetooth (optional) via USB adapter
• VNC remote control
• Android & Apple App

Power Quality
IEC 61000-4-30 Class A Edition 3
IEEE 1159: 2009

Power
IEEE 1459: 2000

Harmonics
IEC 61000-4-7 Class 1: Edition 2 (2008)
IEEE 519:2014

Voltage Flicker
IEC 61000-4-15: Edition 2 (2010)
IEEE 1453: 2011

Compliance/Testing
EN 50160: 2010

Power/Energy – 1 Second sampling
• Real Power (W) – P: meets 0.2S requirements, range probe dep.
• Apparent Power (VA) – S: meets 0.2S requirements, range probe dep.
• Reactive Power (var) – Q: meets 0.2S requirements, range probe dep.
• Power Factor (W/VA) -”true” 1 to 0 to 1
• Displacement PF -1 to 0 to +1
• Demand (in W): meets 0.2S requirements, range probe dep.
• Energy (in Wh): meets 0.2S requirements, range probe dep.

Distortion – 200ms, 3 sec, 10 min windows
• Vthd: 0-100%, +/- 5% for V>=1% Vnom,
• V Ind Harm: DC, 2-127, +/- 5% for V>=1% Vnom
• Ithd: 0-100%, +/- 5% for V>=1% Vnom,
• I Ind Harm: DC, 2-63, +/- 5% for V>=1% Vnom

Misc.
• Pst – 10 minutes: 0.2-10, +/- 0.05 @ Pst=1 (50/60Hz only)
• Plt – 2 hours: 0.2-10, +/- 0.05 @ Pst=1 (50/60Hz only)


© Copyright 2023 Power Quality (Thailand) Co., Ltd. All Rights Reserved.